This 2 pair 22AWG screened cable is manufactured as an equivalent to Belden 8723 and is commonly used for instrumentation, control and signal transmission where protection from electrical interference is required. Each pair is individually foil-screened, helping to maintain signal integrity in electrically noisy environments.
The cable uses stranded tinned copper conductors, making it suitable for installations that require flexibility during termination or routing within panels, trays or containment. The LSZH (Low Smoke Zero Halogen) outer sheath meets CPR Euroclass Eca requirements and is designed for use in buildings where reduced smoke and corrosive gas emissions are preferred in the event of fire.
Typical applications include BMS systems, control panels, instrumentation circuits, audio/control signalling and data transmission within commercial or industrial installations. The cable construction closely matches Belden 8723, making it suitable for projects specifying that cable type or its equivalent.
Specification
| Outer Sheath |
LSZH Ø4.20mm |
| EN50575 CPR Class |
Eca |
| Conductor |
Stranded Tinned Copper Wire |
| Conductor Size |
22AWG (7/0.25) |
| Number of Pairs |
2 Pairs |
| Insulation |
HDPE (0.21mm) Ø 1.20mm |
| Screening |
Individual Aluminium Foil Screened Pairs |
| Drain Wire |
Common 24AWG Drain Wire |
| Outer Sheath Colour |
Grey |
| Conductor DC Resistance |
54.2 [Ω/km] |
| Rated Temperature |
-25 to +80°C |
| Minimum Installation Temperature |
-5°C |
| Rated Voltage |
600V |
| Insulation Resistance |
>200 [MΩ/km] |
| Nominal Capacitance |
115pF/M [±10%] |
| Velocity Ratio |
66% |
| Nominal Impedance |
45Ω |
| Voltage Drop (@380V/100M, 1A) |
≤3.42V |
| Pair 1 |
Red/Black |
| Pair 2 |
Green/White |
| LSZH Sheath Meets: |
IEC60332-1 [Flame Propagation] IEC60754 [Halogen Free] IEC61034 [Smoke Emissions] |
This cable provides a practical solution for installers needing a Belden 8723 equivalent screened instrumentation cable suitable for internal building installations.